CVSS v3.1
7.5
EPSS
0.65%
Published
Jul 26, 2023
Modified
Nov 21, 2024
Public PoC / Exploit
All weaponized →No public PoC or exploit code indexed for this CVE.
Links to public security research (Exploit-DB, Nuclei, Trickest, GitHub) for defensive use only.
Description
A vulnerability exists in the HCI IEC 60870-5-104 function included in certain versions of the RTU500 series product. The vulnerability can only be exploited, if the HCI 60870-5-104 is configured with support for IEC 62351-5 and the CMU contains the license feature ‘Advanced security’ which must be ordered separately. If these preconditions are fulfilled, an attacker could exploit the vulnerability by sending a specially crafted message to the RTU500, causing the targeted RTU500 CMU to reboot. The vulnerability is caused by a missing input data validation which eventually if exploited causes an internal buffer to overflow in the HCI IEC 60870-5-104 function.
CVSS Vector
CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:HWeaknesses (CWE)
Affected Products (5)
References (2)